1300(A) Fault Isolator Module
FEATURES
- Powered by SLC loop direcy, no external power required.
- Mounts in standard 4 (10.16 cm)square, 2.125” (5. 3975 cm) deep
junction boxes.
- Integral LED blinks to indicate normal condition. Illuminates steady
when short circuit condition is detected.
- High noise (EMF/RFI) immunity.
SPECIFICATIONS
- Operating voltage: 15— 28 VDC (peak).
- Maximum current upon activation due to short circu it: refer
to the manual for the main FACP.
- Standby current: 450 pA maximum; 1300(A) is not isolating —
relay closed.
- Temperature range: 32°F to 120°F (0°C to 49°C).
- Relative humidity: 10% to 93%.
- Weight: 150 grams (5 oz.).
|