fire alarm system>>Protect
wire
>>
Conventional Panel SRP 4x4
..............................................................................................................................................................................................................................................................
Features
Four zone fire
alarm control and release panel
Initiating
circuits capable of Class A
Field selectable
input and output configurations
Ground fault
detection
Lamp and system
trouble test
Protect
wire
Alarm Point Location Meter available
Specifications
Enclosure
16 gauge steel
with piano hinged door.
Size: 20.5 in.
(H) x 14.5 in. (W) x 4.7 in. (D) (52 cmx 37 cmx 12 cm)
Initiating Device Circuits:
Four
Class A or B (Style D or B) Alarm Circuits and one dedicated
Class B (Style B) Supervisory Circuit.
Maximum
length of Protect wire Linear Heat Detector per circuit:
3,500 feet (1,067 m).
Two
Wire
Smoke Detector capacity per circuit: 20 - 0.045 mA
type as supplied by The Protect wire Company.
Output Circuits
Alarm
Indicating, Trouble Indicating, Supervisory, or Releasing.
Four
Class B (Style Y) Output Circuits, reverse polarity on alarm.
Optional
Class A (Style Z) AM-91-2 Module available.
Output
1, dedicated to Common (General) Alarm signaling,
rated 24 V FWR, 1 amp continuous. Outputs 2, 3, and 4 are rated
at 1 amp each, 2.1 amp combined.
Outputs
2, 3, and 4 are provided with a common disconnect
switch.
UL
listed compatible Solenoids (see manual) and FM Solenoid
Groups A, B, D, E, F, G & H.
Outputs
Remote
Signaling SPDT Relays rated 3 amp, 30 VDC for Alarm,
Trouble, and Supervisory.
Auxiliary
Power - Regulated 24 VDC, rated 100 mA max. (Power
Limited).
Input Power
120
VAC +10 –15% - 100 VA max. (240 VAC available).
Approvals:
Factory
Mutual
UL
listed
California
State Fire Marshal #7165-0854:104 |