Fire Alarm Systems >> Fire Lite Alarms >> H355(A)

.............................................................................................................................................................................................................................................................

H355(A) Series Intelligent Addressable Thermal (Heat) Detectors for MS-9600, MS-200UD

FEATURES

      SLC loop:

  • Two-wire SLC loop connection.
  • Unit uses base for wiring
  • Addressable by device.
  • Direct Decade 01 – 159 (MS-9600), or 01 – 99 (MS-9200UD) entry of address.

      Architecture:

  • Sleek, low-profile, stylish design.
  • State-of-the-art thermistor technology for fast response.
  • Integral communications and built-in device-type identification.
  • Built-in tamper resistant feature.
  • Built-in functional test switch activated by external magnet.

      Operation:

  • Factory preset at 135°F (57°C).
  • Rate-of-rise model (H355R), 15°F (8.3°C) per minute.
  • 360°-field viewing angle of the visual alarm indicators (two bicolor LEDs). LEDs blink green in Normal condition and turn on steady red in Alarm.
  • Visible LEDs “blink” every time the unit is addressed.

SPECIFICATIONS

Diameter: 6.1" (15.5 cm) installed in B350LP.

Height: 2.1" (5.33 cm).

Weight: 4.8 oz. (137 g).

Installation temperature: –4°F to 100°F (–20°C to 38°C).

Humidity range: 10% to 93% relative humidity (non-condensing).

Voltage range: 15 to 32 VDC peak.

Standby current: 300 μA @ 24 VDC (one communication every 5 seconds with LED blink enabled).

LED current: 6.5 mA @ 24 VDC.

Mounting: B350LP flanged base, included.

Fixed-temperature setpoint: 135°F (57°C).

Rate-of-rise detection: responds to greater than 15°F/ 8.3°C per minute.

Recommended spacing: 50' (15.24 cm) for both 190° fixed and 135° fixed/rate-of-rise models (UL and FM listed distances).

 

 