Fire Alarm Systems >> Fire Lite Alarms >> MS-9200UDLS(E).............................................................................................................................................................................................................................................................MS-9200UDLS(E) Intelligent Addressable FACP with Built-In CommunicatorFeatures
Electrical SpecificationsAC Power:MS-9200UDLS: 120 VAC, 60 Hz, 3.0 amps. MS- 9200UDLSE: 240 VAC, 50 Hz1.5 amps. Wire size:minimum 14 AWG (2.00 mm˛) with 600 V insulation. Battery:Two 12 V 18AH lead-acid batteries. Battery charger capacity: 7 – 18 AH. MS-9200UDLS cabinet holds maximum of two 18 AH batteries. Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Each terminal block provides connections for two Style Y (Class B)
or one Style Z Two Programmable Relays and One Fixed Trouble Relay:Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). Form-C relays. Special Application Power (24 VDC Nominal):Jumper selectable (JP4) for conversion to resettable power output. Up to 0.5 amps total DC current available from each output. Power-limited.
|