Fire
Suppression system >> Ansul- USA >> cleanguard
........................................................................................................................................................................................................................................................................

Features
Economically
priced
Meets
or exceeds requirements of ANSI/UL 2129 and 711
Listings
and approvals include UL, ULC, and FAA
Simple
operation and maintenance
Tough,
glare-resistant, one-piece mylar nameplates
Rechargeable
Manufactured
of durable high quality materials
Operating
temperature range is –40 °F to 120 °F (–40 °C to 49 °C)
Large,
easy-to-read pressure gauge
Hand
portable fire fighting training at the world renowned ANSUL Fire School
Six-year
limited warranty from date of delivery to original end-user purchaser
Sold
and serviced through a network of independent distributors in
every state and most foreign countries
Application
CLEANGUARD® extinguishers are designed for protection of light and
ordinary hazards. These compact and portable extinguishers are suited
for both industrial and commercial
fire protection needs.
Typical applications include:
Computer
rooms
Essential
communication areas
Irreplaceable
data, document, and art storage rooms
Laboratories
Sensitive/expensive
equipment
Specifications
|
Model
|
FE02VB |
FE05 |
FE09 |
FE13 |
|
Ext. Part No. (UL) |
429107 |
429020 |
429021 |
429022 |
|
Ext. Part No. (ULC) |
429596 |
429597 |
429598 |
429599 |
|
Bracket Part No. |
24610 – (Included) |
429146 |
422737 |
30937 |
Agent Capacity .
(DuPont FE-36) |
2.5 lb. (1.1 kg) |
4.75 lb(2.2 kg) |
9.5 lb.(4.3 kg) |
13.25 lb.(6 kg) |
|
Charged Weight. |
5.0 lb.(2.3 kg) |
9.5 lb. (4.3 kg) |
21.81lb(9.9 kg) |
25.63 lb. (11.63 kg) |
|
Discharge Time |
9.0 seconds |
8.6 seconds |
9.5 seconds |
13.5 seconds |
|
Agent Flow Rate |
0.30 lb./sec. (.14 kg/sec.) |
0.60 lb./sec. (.27 kg/sec.) |
1.15 lb./sec. (.52 kg/sec.) |
1.12 lb./sec. (.51 kg/sec.) |
|
Listings/Approvals |
UL/ULC |
UL/ULC/FAA /USCG
|
UL/ULC/FAA /USCG
|
UL/ULC/FAA /USCG |
|
USCG Classification (Marine) |
— |
Type B:C, |
Type B:C, |
Type B:C, |
|
UL/ULC Rating
|
2-B:C |
5-B:C |
1-A:10-B:C |
2-A:10-B:C |
|
Effective Range |
8-10 ft.(2.4-3.1 m) |
10-12 ft. (3.1-3.7 m) |
14-16 ft. (4.3-4.9 m) |
14-16 ft.(4.3-4.9 m) |
|
Dimensions Height . |
14 1/4 in. |
17 in |
18 3/4 in. |
22 1/2 in. |
|
Width |
5 3/4 in. (146 mm) |
8 1/2 in.(216 mm) |
9 in.(229 mm) |
9 1/2 in. (241 mm) |
|
Depth |
3 3/8 in. (86 mm) |
4 7/16 in. (113 mm) |
7 in. (178 mm) |
7 in. (178 mm) |
|
Fire Suppression Capability |
|
UL Panel Class A |
N/A |
N/A |
8 ft. x 8 ft. (2.4 m x 2.4 m) Panel |
10 ft. x 10 ft. (3.1 m x 3.1 m) Panel |
|
Novice Operator* Class |
B 2 sq. ft. (.19 sq. m) |
5 sq. ft. (.47 sq. m) |
10 sq. ft. (.93 sq. m) |
10 sq. ft. (.93 sq. m) |
|
Experienced Operator Class B
|
5 sq. ft. (.47 sq. m) |
12.5 sq. ft. (1.2 sq. m) |
25 sq. ft. (2.3 sq. m) |
25 sq. ft. (2.3 sq. m) |