fire alarm system
>> cTEC
...................................................................................................................................................................................................................................................................
|
 |
Offering high performance at a competitive
price, the AFP one or two loop analogue addressable fire panel
supports System Sensor, Nittan or Apollo XP95 protocols.
Fullycompliant with EN54 Parts 2 and 4, it's wide range of
features include 16 zonal alarmLEDs (expandable to 32), four
separate independently programmable sounder circuits andan
integral 24V 3amp switch mode power supply. The AFP can be
programmed on-site viatactile switches on the panel front or via
an easy to use, low-cost upload/download PCprogramme. Other
features include a 999 event memory, delay timer and
phasedevacuation facilities, sophisticated test and maintenance
facilities and a comprehensive'auto-learn' facility allowing the
panel to self-configure to devices connected to the loop.
16
zonal alarm leds provided as standard,expandable to 32 via
AFP703 extension LED kit.
Compatible
with Apollo XP95, System Sensor or Nittan protocols.
Panel
supplied with one integral loop driver, expandable to two via
AFP702 plug-on loop driver.
Easy-to-read
80 character back-lit display
40
characters of custom text available per device
Four
separate independently programmable sounder circuits rated at a
total of 3A.
Powerful
short circuit protected loop drivers.
Up to
32 loop driven sounders per loop.
Integral
24V 3A EN54 switch mode psu, rated @ 185-260Vac, 50-60 Hz.
Alert,
Reset, Silence and Class Change inputs.
Fire,
Fault, Pre-alarm, Reset and +24V Aux. outputs
Remote
Signal Output (to remote manned centre).
Space
for 7AHr sealed lead acid batteries.
Earth
fault monitoring.
999
event memory.
Programmable
sounder/remote output delay facilities (per zone)
Phased
evacuation facility
RS232
port provided for connection to external serial printer or
upload/download PC.
One
AFP711 Network Driver Card (fitted to theRS485 port on the
master panel) allows the connection of up to 15 AFP Repeaters
per system (Repeaters are not compatible with AFPE Economy
Panels).
Sophisticated
test and maintenance facilities.
Panel
can be programmed on-site via tactile switches on panel front or
via an easy to use, low-cost upload/ download PC programme.
Comprehensive
‘Auto-Learn’ facility allows panel to self configure to devices
connected to the loop.
Push
button entry code access protection.
Detailed
description of faults on LCD display.
Intuitive
language-free legend on main label allows cost-effective customizing of
smaller label with customers own logo and/or foreign language text.
Specifications
|
POWER SUPPLY SPECIFICATION |
|
Mains supply
voltage |
230 Va.c. 10%
50/60Hz |
|
Internal power
supply |
27Vd.c. |
|
Total output
current limited to |
3A @ 230 Va.c.
(1.5A on AFPE) |
|
Auxiliary power
output |
27 Vd.c. Nominal
monitored |
|
for failure |
Yes |
|
Battery charger
monitored for failure |
Yes |
|
Batteries
monitored for disconnection & failure |
Yes |
|
Quiescent
current drain (1 loop unloaded) |
<80mA |
|
Quiescent
current drain (2 loop unloaded) |
<100mA |
|
Earth fault
monitoring |
Yes - any
conductor to Earth |
|
Temperature
compensated charging |
Yes |
|
DETECTOR LOOP DRIVER SPECIFICATION |
|
Maximum
number of Loop Drivers allowed
|
2 (1 on AFPE) |
|
Maximum cable length per
loop |
1Km |
|
Line Fault monitored for
Open Circuit
|
Yes |
|
Line Fault monitored for
Short Circuit
|
Yes |
|
Onboard loop
isolators with LED indication when active |
Yes |
|
Auto-Polling
from each loop end |
Yes |
|
Maximum allowable loop
impedance (each conductor) |
20 Ohm |
|
Maximum cable
capacitance |
.27uF |
|
Maximum loop output
current |
350mA |
|
Peripheral modules
supported |
Yes - as detailed in
manual. |
|
Max no. addressable
points per loop (Apollo XP95) |
126 |
|
Max no. addressable
points per loop (System Sensor) |
99 sensors + 60 modules |
|
LOOP POWERED SOUNDERS |
|
Number of
programmable Groups |
15 |
|
Maximum number per loop
(Apollo XP95)
|
32 |
|
Maximum number per loop
(System Sensor)
|
32 |
|
PANEL CONVENTIONAL SOUNDER CIRCUIT SPECIFICATION |
|
Number of Programmable
circuits |
4 |
|
End of Line Resistor
Value |
6800 Ohm 5% Tol. 0.25W |
|
Line Fault monitored for
Open Circuit
|
Yes |
|
Line Fault monitored for
Short Circuit
|
Yes |
|
Outputs fused at |
1 Amp |
|
Maximum total output
current all outputs
|
3 Amps (1.5Amps on AFPE) |
|
Maximum No. of Bells @
25 mA |
120 (60 on AFPE) |
|
Maximum No. of
electronic sounders @ 20 mA |
150 (75 on AFPE) |
|
AUXILIARY OUTPUTS |
|
Max sink current |
100mA each (300mA total) |
|
Type |
Open Collector |
|
Max open circuit voltage |
27Vd.c. |
|
Reset Output |
Active low during reset cycle |
|
Remote Output (to manned
centre) |
Active low during any fire
condition + isolate/delay facility |
|
Pre-Alarm Output |
Active low during any pre-alarm
condition |
|
Fire1 Output |
Active low during any fire
condition |
|
Fire2 Output |
Active low during any fire
condition unless silenced |
|
Fault |
Active low when NO faults are
present - failsafe to o/c |
|
24v Aux Power Output |
1 Amp - fuse |
|
FUSES |
|
Mains Fuse |
1A HRC Ceramic 20mm |
|
Sounder Outputs (F1, F2, F3, F4) |
1A F 20mm |
|
Auxiliary Output (F5) |
1A F 20mm |
|
Battery Fuse |
3A F 20mm |
|
All fuses compliant to IEC (EN60127
PT2) |
|
|
AUXILIARY INPUTS |
|
Reset |
0V Trigger (active low) |
|
Silence |
0V Trigger (active low) |
|
Class Change
(Evacuate) |
0V Trigger
(active low) |
|
Alert (Phased Evacuate) |
0V Trigger (active low) |
|
CONNECTION BLOCK |
|
Plug on Type - largest acceptable
conductor size = 1.5mm |
|
FRONT PANEL CONTROLS & INDICATORS |
|
Control Buttons |
Silence,
Reset, Evacuate |
|
Scroll/Menu Access
Buttons |
Up (1);
Down (2); Accept (3); Abort (4) |
|
Liquid Crystal Display |
2 lines
x 40 Characters (backlit) |
|
LED Indicators |
1 x
General Fire (red) |
| |
16 x
Zonal Fire, expandable to 32 (all red) |
| |
1 x
System Energised (green) |
| |
1 x PreAlarm (amber) |
| |
1 x
Remote Output Activated (red) |
| |
1 x
Menus Accessed (amber) |
| |
1 x
Disablement (amber) |
| |
1 x Test
(amber) |
| |
1 x
Remote Output Disabled (amber) |
| |
1 x
Silenced (amber) |
| |
1 x
General Fault (amber) |
| |
1 x
System Fault (amber) |
| |
1 x
Sounder Fault (amber) |
| |
1 x PSU
Fault (amber) |
|
APPROXIMATE DIMENSIONS |
|
Back Box (W x H x D) |
410 x 250
x 80mm (metal) |
|
Lid (W x H x D) |
435 x 270
x 5mm (metal) 439 x 274 x 7mm (plastic) |
|
Weight (without
batteries) |
4.5Kg |
|
CABLING |
|
Fire proof, screened cable (min. size
1mm) |
|
PROGRAMMING & PRINTER CONNECTION |
| 2 x RS232 |
1 x Plug
on connector and 1 x 0.1 Molex header |
|
PROGRAMMING METHODS |
|
On site using the AFP's fascia
buttons |
|
On or off-site using a
Windows-based PC running the AFP upload/download
software. |
|
MENU ACCESS LEVELS |
|
Access Level 1 |
Scroll events |
|
Access Level 2 |
Silence, Reset, Evacuate |
|
|
Override delays |
|
|
View active Fire, Pre-Alarms, Faults & Disablements |
|
|
Disable / Enable Points, Zones and Outputs |
|
|
Set time and date |
|
|
Change User PIN code |
|
|
Review event log |
|
Access Level 3 |
View and edit Point information |
|
|
View and assign a zone's sounder configuration |
|
|
Set delays / Assign phased evacuation |
|
|
Set next maintenance date |
|
|
Change User and Engineer PIN code |
|
|
Invoke Commissioning utilities |
|
|
Invoke Test and Maintenance utilities |
|
|
Clear event log |
|
SITE SPECIFIC DATA |
|
User and Engineer Pin Code |
|
40 Characters free text for company
name, etc |
|
Next due
maintenance date |
|
Data
protected by internal manual link |
| Configuration may be edited via
front panel buttons or a PC programmed running Windows
95. |
|
We reserve the right to alter product
specifications without prior notice.
Errors and omissions excepted. |