fire alarm system >>
Protectowire
>>
Sharpeye IR FLAME detector
..............................................................................................................................................................................................................................................................................
Features
Triple IR
spectrum design
Sensitivity
selection
User
programmable configuration
Automatic and
manual built-in test
Explosion-proof
Standard 4 wire
connection
FM, CSA and
CENELEC Approved
General Specifications
|
Spectral response |
| Detection
range |
1 sq. ft.
gasoline fire at 200 ft. (60 m.)*
1 sq. ft. diesel oil fire at 100 ft. (30 m.)*
1 sq. ft. alcohol fire at 100 ft. (30 m.)*
2 sq. ft. JP4 fire at 100 ft. (30 m.)* |
| Response time |
Typical 2
seconds.
Adjustable time delay up to 30 seconds. |
| Time delay |
Adjustable time delay up to 30 seconds |
|
Electrical |
| Operating
voltage |
18-32 VDC |
| Power
consumption |
150 mA in
standby
200 mA in alarm |
| Electrical
interface |
Standard
4-wire
connection with cascading capability.
Complete electrical interface protection. |
|
Electrical connection |
| Standard |
3/4 in. 14NPT
conduit |
| Fault
accessory |
5 Amps at 30
VDC
5 Amps at 250 VAC |
|
Environmental tests |
| High temp-
Method |
501.1 Proc. II |
|
Low temp- Method |
502.1 Proc. I |
|
Humidity - Method |
507.1 Proc. IV |
|
Salt Fog - Method |
509.1 Proc. I |
|
Dust- Method |
510.1 Proc. I |
|
Vibration - Method |
514.2 Proc.VII |
|
Mechanical Shock- Method |
516 Proc. |
|
Temperature range |
|
Operating |
-40°F (-40°C) to 160°F (70°C) |
|
Storage |
-40°F (-40°C) to 160°F (70°C) |
|