Our Products

Fire Alarms Systems  
Fire Suppression Systems  
Security Systems  
Perimeter Protection  
Building Management System  
Home Automation System  
Cables  

Please Click Here

fire alarm system >> system sensors >> heat detector 5351

...........................................................................................................................................................................................................................................................................

 

Features

Low profile design

Low current draw

Backward compatible with Series 100 detector   range of bases

Wide operating voltage 8 to 30VDC

Bi-colour LED detector status indicator

Programmable sensitivity

Addressable feature

Advanced maintenance features via remote hand-held test unit

Range of detector bases available

Approved to EN54 – 5:2000 Class A1R (Amendment 1)

Architectural/Engineering Specifications

5351E Rate of Rise & Fixed Temperature Thermal Detector

In addition to the comprehensive programming tool, a simple laser based alarm test unit is also available. The coded signal transmitted by this device can instruct the detector to generate a full alarm condition at a range of up to 5 meters from the detector, and is an ideal tool for initial commissioning and routine system testing. A variety of detector bases can be used with the 5351E detector, providing application flexibility and compatibility with a wide range of Fire Alarm Control Panels. All bases are fitted with a shorting spring to permit circuit testing prior to fitting the detector and have a tamper resistant feature, which when activated prevents removal of the detector without the use of a tool. All System Sensor products are covered by our extended 3 year warranty.

Electrical Specifications

Operating Voltage Range 8 to 30VDC (Nominal 12/24VDC)
Typical Standby Current @ 25°C 60μA @ 24VDC (LED no blink)
Maximum Permissible Alarm Current (LEDOn) 80mA @ 24VDC (Limited by panel)

Environmental Specifications

Operating Temperature Range -30°C to +70°C
Humidity 5 to 95% Relative Humidity
(non condensing)

Mechanical Information

Height 48mm (plus 9mm for B401 base)
Diameter 102mm
Weight 105g (plus 60g for B401 base)
Wire Gauge for Terminals 0.75mm2 to 2.5mm2
Colour Pantone, warm grey 1C
Material Bay blend FR110

Product Range

Bases (see notes) B401 Standard Base B401SD Standard base with schotty diode
B401R Resistor base with 470 ohm resistor B401RSD Standard base with 470 ohm resistor and Schotty diode
B401RM Standard recess base with 470 ohm resistor B401DG Deep base
B401DGR Deep base with 470 ohm resistor B401DGSD Deep base with Schotty diode
B312NL 12V non-latching relay base B312RL 12V latching relay base
B324RL 24V latching relay base
Accessories

S300RPTU Remote Programming and Test Unit S300RTU Remote Test Unit
S300SAT Remote Programming Interface Unit S300ZDU Zonal Display Unit

Other Detectors

2351E, 2351TEM, 4351E, 5351TE

 

|Home |Profile|Services|Channel Partners|Clients|Downloads|Careers|Online Enquiry|Contact Us|Sitemap|