fire alarm system >> cooper >> Loop Beacon

.........................................................................................................................................................................................................................................................................

 

 

Integrated sounder beacons

 

The CASB range of loop-powered addressable wall sounder beacons offer a highly efficient, low current sounder beacon option. Sounder volume and tone are set at the analogue panel avoiding the need to access each sounder individually to alter settings.

Specifications

Model

CASBB384

CASB383

CASB383-WP

Operating voltage

  17 to 32V dc

Tones (set by panels) Continuous 910 Hz Pulsed 910 / 0 Hz @ 1Hz Two tone 610 / 910 Hz @ 1Hz cycle Slow whoop Continuous 910 Hz Pulsed 910 / 0 Hz @ 1Hz Two tone 644 / 984 Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 sec / 0.5 sec gap
Sound output (set by panel) +/- 3 dB Low volume: 77 dB
Medium volume: 89
High volume: 90 dB
Low volume: 87 dB
Medium volume: 93
High volume: 100 dB
Current consumption

Low volume: <7mA
Medium volume: <8mA
High volume: <9mA  

Standby current

<320µA

Construction

 PC ABS

Operating temperature

-10°C to +55°C (95% RH)

Colour

                    White

    Red

IP rating

            IP40

IP42  IP66
Dimensions HxWxD (mm) 115 (Dia) x 42 (D) 105x105x95 108x108x103
Weight 0.2Kg 0.25Kg 0.57Kg