Fire Alarm Systems >> Fire Lite Alarms >> MS-9600 Rev. 2/DACT-UD

.............................................................................................................................................................................................................................................................

MS-9600 Rev. 2/DACT-UD: Intelligent Addressable FACP with Optional 2nd Loop

Features

  • SLC can be configured for NFPA Style 4, 6, or 7 operation.
  • SLC supports up to 318 addressable devices per loop (159 detectors and 159 monitor, control, or relay modules), including the new addressable dual-monitor module, heat
    detectors, and duct detector.
  • SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG (3.31 mm²). Requires twisted, shielded wire (3,000 ft./914.4m untwisted, unshielded wire).Modular concept
  • Four onboard NACs with additional NAC capability using output control modules (CMF-300 or CMF-300-6).
  • Silence Inhibit and Auto Silence timer options.
  • Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability.
  • Selectable strobe synchronization per NAC.

Specification

AC Power – TB1: 120 VAC, 60 Hz, 3.0 A. Wire size: minimum 14 AWG (2.08 mm²) with 600 V insulation.

Battery (lead acid only) – TB2: Maximum charging circuit: Normal flat charge 27.6 VDC @ 1.0 A. Maximum battery charger capacity: 25 AH. MS-9600 cabinet holds maximum of two 18 AH batteries. For 25 – 120 AH batteries, use the CHG- 120F or CHG-75 Battery Charger and BB-55F Battery Box.

NOTE: Jumper JP3, on the FACP main circuit board, must be cut to disable the FACP battery charger when using the CHG- 120F.

Communication Loop – (standard) TB8: 24 VDC nominal, 27.6 VDC maximum. Maximum length: 10,000 ft. (3048 m) total twisted, shielded pair length. Maximum loop current: 400
mA (short circuit) or 100 mA (normal). Maximum loop resistance:
40 ohms. Supervised and power-limited.

The maximum available current shared between all NACs and auxiliary power outputs is 7.0 A at 24 VDC.

Notification Appliance Circuits – TB4: Power-limited circuitry. Maximum voltage drop in wiring: 2.0 VDC. Nominal operating voltage: 24 VDC. Current limit: fuseless, electronic, power-limited circuitry. Maximum signaling current per circuit: 3.0 A. End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL listed) for NACs. Refer to Fire Lite Device Compatibility Document for listed compatible devices.

Programmable and Trouble Output Relays – TB5: Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays.

Four-Wire Resettable Smoke Detector Power (24 VDC nominal) – TB3, Terminals 1(+) & 2(–): Maximum ripple voltage: 10 mVrms. Up to 3.0 A for powering four-wire smoke detectors. Power-limited circuit. Refer to Fire Lite Device Compatibility Document for listed compatible devices.

Nonresettable Power #1 (24 VDC Nominal) –TB3, Terminals 3 (+) & 4 (–): Maximum ripple voltage: 10 mVrms. Up to 0.5 A total DC current available from each output. Power-limited
circuit. TB3, Terminals 5 (+) & 6 (–): non-resettable power #2.

EIA-485 (ACS) – TB6: ACS annunciator connector, Terminal 1 (+) and Terminal 2 (–).

EIA-485 (TERM) – TB7: Terminal mode annunciator connector, Terminal 1 (Out +), 2 (In +), 3 (Out –), 4 (In –).

EIA-232 – TB8: PC/printer connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)

Cabinet Specifications

Door: 18.67" (47.43 cm) high x 15.78" (40.08 cm) wide x 1.08" (2.74 cm) deep. Backbox: 18.50" (47.0 cm) high x 15.50" (39.37 cm) wide x 4.37" (11.1 cm) deep. Trim Ring (FC-TR):
21.62" (54.92 cm) high x 18.62" (47.3 cm) wide.