fire alarm system >> sensitron  - italy

........................................................................................................................................................................................................................................................................

 

 

Description

The LCR 2 gas detector is designed and manufactured to offer the user a cost effective product with professional features, in comparison with the currently common detectors on the market.

The professional Catalytic sensor (Pellistor) employed for the flammable Gas detection, shows an excellent output linearity up to 100 % LEL as well as a superior repeatability and durability.

Distinguishing features of the Catalytic detector are: very high stability of the zero point, linear response, short period, longer lifetime and response Selectivity.

The LCR 2 can also be equipped with a three electrodes Electrochemical Cell designed for the detection of the CO (Carbon Monoxide) in concentrations up 500 ppm (part per million) for car park areas.

The LCR 2 series detectors provide an Analog 4-20 mA output signal proportional to the gas being detected. 4 mA corresponds to fresh air (no gas leakage) while 20mA corresponds to 100% LEL (Lower Explosion Limit) for explosive gases and 500 ppm for CO (Carbon Monoxide).

The LCR 2 gas detectors are designed to be connected to any control unit or PLC accepting a 4-20mA input signal.

On the LCR 2 there is a green led placed on the main PCB that will light up when the detector is powered. The LCR 2 can be provided with two different enclosures, DUST IP55 or certified Explosion Proof.

LCR 2 detectors comply with he ATEX certification for the equipments to be employed in potentially Explosive

Specifications

 

Characteristic technique

Technical specifications

 

Sensor catalytic (perla versione gasinfiammabili) Cella elettrochimica(per il Monossido dicarbonio)

Catalytic sensors (for
the flammable gas
version) Electrochemical Cell sensor (for Carbon
Monoxide)
NET-PEL NEMOTO
NET-CO NEMOTO
Tensione di
alimentazione
Power supply 12-24 Vdc +/-10%
Consumption current  Current consumption Versione gas infiammabili (CH version) 90 mA a/at 12 Vdc e/and 60 mA a/at24Vdc.Versione perCO (CO version) 40mA a/at 12 e/and24Vdc
Micro processor  Microprocessor No/None
Uscita proportional Proportional output 4-20 mA
Tempo di risposta Response time T90 <60sec
Repeatability Repeatability ± 5% FS
Temperature distoccaggio Storage temp -25 / + 60 °C
Temperature operative
Humidity relative
Operation temp.
Relative Humidity
-10 / + 40 °C0-90   noncondensate /  not condensed
Peso Weight Exd 700 gr. Dust 400 gr
Dimensions Dimensions Exd: L.110, H.185, D.90 mmDUSTL.106,H.180,D.65 mm.